XM31-915-HP
Power Supply
 
 

Alarms
 

Battery
 

Power Supply
Model ALPHA/XM31-915-HP
Firmware V2.07.0
Major Alarm OK
Minor Alarm OK
Operational Mode Line
Charger Mode Rest
Tamper Door closed
Power Supply Language English
Power Supply Priority Normal
Input
AC Line Mode OK
Voltage 123.22 V
Current 5.71 A
Power 605 W
Frequency 60 Hz
Tap Status Normal
Frequency Range 3.00 Hz
Current Limit 17.00 A
Input Power Consumption 3,814 Wh
Output
Voltage 88.06 V
Power 480 W
Apparent Power 534.52 VA
Frequency 60.01 Hz
Percent Load 40.50 %
Output Setting 90 V
Output Regulation Fine
Over-current Tolerance 3.000 sec
Retry Delay 60 sec
Retry Limit 20
Active Drop Alarm OK
Active Drop Threshold 50 W
Current 6.07 A
Inverter
Inverter Status Off
End of Discharge Type String
End of Discharge Level 1.70 V/cell
Reduced Peak Mode Disable
Total Standby Events 29
Time Since Last Standby Event 206d 1h:23m
Time in Last Standby Event 0d 0h:01m
Total Time in Standby 352 min
Standby Events Since Reset 6
Time in Standby Since Reset 3 min
Time Since Reset 334 day(s)
Total Run Time 334 day(s)
Transformer Run Time 334 day(s)
Total Downtime 0d 0h:00m
Oil Cap Lifespan Consumed 9.8 %
Self Test
Deep Discharge Cycle Timed
Test Countdown 6 day(s)
Test Duration 10 min
Test Interval 30 day(s)
Test Inhibit No

 
Copyright © 2017-2025 EnerSys. All Rights Reserved.