XM31-915-HP
Batteries
 
 

Alarms
 

Battery
 

Batteries
Battery String Voltage 39.01 V
Estimated Runtime At least 4 hours
Battery Life Remaining Over five years
Battery Balancing Disabled
Balancing String Not balancing
Battery System Configuration 1 string of 3 batteries
Battery Temperature 25 °C
77 °F
  1 2 3 Balancing
String A 13.03 V 13.04 V 13.02 V Normal
Battery Charging
Charger Mode Rest
Current Charger Mode Time 625 min
Charger Current 0.01 A
Charger Current Limit 10.50 A
Charger Enable Yes
Configuration
Technician ID 0
24 Hour Battery Refresh No
Battery Model 4.0HP
Accept Voltage 2.35 V/cell
Float Voltage 2.25 V/cell
Refresh Voltage 2.45 V/cell
Battery Capacity 114 Ah
Temperature Compensation 4.00 mV/cell/°C
HP Battery Rest Mode Yes
Battery String Detect Auto
Number of Battery Strings 1
Heater Mat Installed No
Conductance
Last Conductance Measurement 2025-05-01
  Last Adjusted Conductance Measurement Manufactured Date
String A Battery 1 1,600 S(℧) 2023-04
String A Battery 2 1,606 S(℧) 2023-04
String A Battery 3 1,600 S(℧) 2023-04

 
Copyright © 2017-2024 EnerSys. All Rights Reserved.